Nowoczesna myśl techniczna

Rigid electroinstallation conduit RSM-PA6-HB

#
#
#
EU designation (EN 61386-1): 33441
Material: self-extinguishing polyamide 6 (PA6)
Mechanical strength: medium (750N) 3
Impact resistance: medium (2,0 kg/100mm) 3
Temperature range (transportation, application, installation):
minimum temperature: -25 °C 4
maximum temperature: +120 °C (Intermittent +180 °C) 4
Flexibility: rigid 1
Colours: transparent white, black other colours on request
Flammability: HB UL94
Application:Rigid conduit is used for distribution and protection of cables in building and industrial electrical installations. Recommended for open places, with an increased risk of fire hazard (wooden constructions, lofts, garrets, etc.) and tightened security against toxic chemical compounds (halogen free). It ensures high strength and resistance to mechanical factors. Pipe has ideally smooth surface. Standard length of the rigid electro-installation pipes is 3 m.
Characteristics of materialFree from halogen, phosphorus and cadmium, self-extinguishing/flame retardant, high-bending and crack resistance, well balanced elongation and elasticity behaviour as well as high abrasion-resistance, high tensile strength, rigidity, high impact strength, very large thermal resistance, resistance to the most of chemical compounds.

Materials:
PA6.6, PA4.6, PA11, PA12 available on request
 
 
 
 
 
 

The specification can be subject of change without notice.

European standard diameters

Nominal diameter DN Inside diameter (mm) Outside diameter (mm)) Coil length (m)
16 14 16 60
20 18 20 45
25 22 25 30
32 29 32 30
40 36 40 21
50 46 50 21
63 58 63 21

All available diameters

Nominal diameter DN Inside diameter (mm) Outside diameter (mm)) Coil length (m)
13 11 13 60
16 14 16 60
18 16 18 60
20 18 20 45
22 20 22 45
25 22 25 30
28 25 28 30
32 29 32 30
37 33 37 21
40 36 40 21
47 43 47 21
50 46 50 21
63 58 63 21
high medium none
Acids weak
strong
oxidising
hydrofluoric
Bases dry halogens
weak
strong
Solvents alkohols
esters
ketones
ethers
chlorinated hydrocarbons
Oils and diesel materials benzene
petrol
diesel mixtures
mineral oils
fatty oils
recommended admissible shoud not be used
Wall installations
Sunk installations
Outer wall installations
Plaster walls
Combustible surfaces (wood, etc.)
Underground installations
Poured concrete
Vibrated concrete
Steamed and vibrated concrete
Electrotechnical equipment
Industrial apparatus, control and automatics
Food and chemical industry facilities
Automotive industry
Shipyard industry
Aircraft industry